MX150 Microprocessor Controller Specifications
Rating Range Switch Dependent
Transfer Type Application Dependent
Switch Type Application Dependent
Undervoltage Dropout for Source 1 and Source 2 75-98% of nominal

Technical Summary

Rating Range
Switch Dependent
Transfer Type
Application Dependent
Switch Type
Application Dependent

Controller Specifications

Undervoltage Dropout for Source 1 and Source 2
75-98% of nominal
Undervoltage Restore for Source 1 and Source 2
85-100% of nominal
Underfrequency Dropout for Source 1 and Source 2
88-98% of nominal
Underfrequency Restore for Source 1 and Source 2
90-100% of nominal
Delay for Engine Cool Down (U)
0-10 seconds
Delay Transfer to Nonpreferred Source (W)
0-5 minutes
Delay NeutralTransition Time Delays (DT,DW)
0-10 minutes
Storage Temperature
(-30˚C - 75˚C ), -22˚F - 167˚F
Operating Temperature Ambient
40 - 400 amp molded shell (-20˚C to 65˚C) , -4˚F to 149˚F
40 - 4000 amp all others (-20˚C to 60˚C), -4˚F to 149˚F