Starting Small... Building Big! With Alban CAT Construction Equipment...

Learn More
Specification Summary
Minimum Rating 1640 ekW
Maximum Rating 2250 ekW
Voltage 220 to 13800
Frequency 60 Hz

Generator Set Specifications

Minimum Rating
1640 ekW
Maximum Rating
2250 ekW
Voltage
220 to 13800
Frequency
60 Hz
Speed
1800 RPM
Height - Maximum
94.9 in
Length - Maximum
234.4 in
Width - Maximum
90 in

Generator Set Configurations

Emissions/Fuel Strategy
Low Fuel Consumption, Low Emissions

Engine Specifications

Engine Model
3516B TA, V-16, 4-Stroke Water-Cooled Diesel
Compression Ratio
14.0:1 Std 15.5:1 HD
Aspiration
TA
Aspiration
TA
Governor Type
Adem™3
Fuel System
Electronic unit injection
Fuel System
Electronic unit injection
Fuel System
7.48 in
Bore
6.69 in
Displacement (HD)
4764.73 in3
Stroke (HD)
8.46 in
Displacement - Std
4210.64 in³
Stroke - Standard
7.48 in
Bore
6.69 in
Displacement - HD
4764.73 in³
Stroke - HD
8.46 in
  • Air Inlet System
    • Air Cleaner; single element canister type
  • Control Panels
    • EMCP 4.2B
    • Emergency stop pushbutton
    • 24 Volt DC operation
    • Environmental sealed front face
    • Text alarm / event descriptions
    • Generator mounted - Rear facing
    • Generator set packages include Caterpillar' s Voltage Regulator. IVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min /max exciter. Limiter and exciter diode monitor
    • Controls: Speed adjust - Auto / start / stop control - Engine cool-down timer - Engine cycle crank - Alarm acknowledge - Lamp test - Load histogram feature - PLC functionality - Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
    • Digital indication for: RPM - DC volts - Operating hours - Oil pressure (psi, kPa or bar) - Coolant temperature - Volts (L-L & L-N) - Frequency (Hz) - Amps (per phase & average) - Power factor (per phase & average) - kW (per phase, average & percent) - kVA (per phase, average & percent) - kVAr (per phase, average & percent) - kW-hr (total) - kVAr-hr (total)
    • Warning / shutdown with common LED indication of shutdowns for: Low oil pressure - High coolant temperature - Overspeed - Emergency stop - Failure to start (overcrank) - Low coolant temperature - Low coolant level -
    • Programmable protective relaying functions: Generator phase sequence - Over / Under voltage (2 7 /59) - Over / under frequency (81 o/u) - Reverse power (kW) (32) - Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
    • Communications: Customer data link (Modbus RTU) - Accessory module data link - Serial annunciator module data link - Cat Connect - 3 Analog inputs - 6 Customer programmable digital inputs
    • Number of I/O varies on options selected: 4 programmable relay outputs (Form A) - 1 programmable relay outputs (Form C) - 1 programmable digital outputs
  • Cooling System
    • Certified standard PGS provided
    • ATAAC - 3516E Package Radiators shipped installed
  • Exhaust System
    • Dry exhaust manifold
    • Flanged faced outlet(s)
  • Fuel System
    • Secondary fuel filters
    • Fuel cooler; not included with packages without radiator
    • Flexible fuel lines - shipped loose
    • Fuel priming pump
  • General
    • Caterpillar yellow with high gloss black rails and radiator
    • Right hand servicing
    • Flywheel and flywheel housing - SAE No. 00
    • SAE Standard rotation
  • Generator and Attachments
    • 3 Phase brushless, salient pole
    • 6 lead
    • Low Voltage: Random wound - Internal excitation - Winding temperature detectors - NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime / 150C standby) - Busbar connections, top center mounted, top cable entry - NEMA standard hole pattern
    • Medium Voltage: Form wound - Permanent magnet - Winding temperature detectors - NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime / 150C standby) - Busbar connections, right side extension box, bottom cable entry - NEMA standard hole pattern
    • High Voltage: Form wound - Permanent magnet - Winding temperature detectors - Anti Condensation Space Heater - Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
  • Governing System
    • ADEM A3
  • Literature
    • English
  • Lubrication System
    • Lubricating oil
    • Gear type lube oil pump
    • Integral lube oil cool
    • Oil filter, filler and dipstick
    • Oil drain lines and valve
    • Fumes disposal
  • Mounting System
    • Rails - engine / generator / radiator mounting
    • Anti-vibration mounts (shipped loose)
    • Rubber anti-vibration mounts (shipped loose)
  • Starting System
    • 24 Volt electric starting motor
    • 45 Amp charging alternator
    • Battery and battery rack w/cables
    • Battery disconnect switch
  • Control System
    • EMCP 4.3, EMCP 4.4
  • Air Inlet System
    • Single element filter
    • Dual element air cleaner
  • Cooling System
    • Standard ambient radiators
    • Air inlet protection including air shut off magnetic switch
    • Standard ambient ATAAC radiators
    • Optional installed radiator
    • Optional installed ATAAC radiators
    • Water level switch gauges
    • Coolant
  • Exhaust System
    • Elbows
    • Flange and exhaust expanders
    • Flanges
    • Flexible fittings
    • Y adapters
    • Mufflers
    • Exhaust Offset
    • Clean emission parets
  • Fuel System
    • Primary fuel filter
  • General
    • US aid emblem
    • Special paint
  • Generators and Attachments
    • 380, 440, 480, 600 Volts, 3 phase, 1800 rpm, RW, IE, No. of leads: 6, Picth: 0.6667 - 1600 Frame
    • 380, 440, 480, 600 Volts, 3 phase, 1800 rpm, RW, PM, No. of leads: 6, Picth: 0.6667 - 1600 Frame
    • 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 phase, 1800 rpm, RW, PM, No. of leads: 6, Picth: 0.6667 - 1600 and 1800 Frames
    • Space heater
    • Generator conversions IE to PM
    • Alternator air cleaner
  • Intrumentation
    • Pyrometer and thermocouples
  • Lube System
    • Lube oil
    • Oil lever regulator
    • Prelube pump groups
  • Crankcase Systems
    • Crankcase protection group: No explosion relief valves; Explosion relief valves
    • Crankcase ventilation system
  • Mounting System
    • Puck style low efficiency isolators
    • Spring type vibration isolators
    • IBC vibration isolators
  • Power Connections
    • Grounding groups
    • Neutral ground connections
    • Center post busbars
    • Right, left side and rear power connections
  • Special Tests / Reports
    • CSA certification
    • IBC certification
    • Special package tests: PGS test report @ 1.0 and 0.8 power factors
    • Standard engine test charge
    • Generator set test report
    • Fuel consumption test
    • Torsional vibration analysis TVA report
  • Starting / Charging Sytem
    • Jacket water heaters