Starting Small... Building Big! With Alban CAT Construction Equipment...

Learn More
Specification Summary
Aspiration Air to Air Aftercooled
Fuel System Electronic unit injection
Minimum Rating 500 ekW
Maximum Rating 600 ekW

Engine Specifications

Aspiration
Air to Air Aftercooled
Fuel System
Electronic unit injection
Engine Model
C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
145 mm (5.71 in)
Displacement
18.13 L (1106.36 in3)
Stroke
183 mm (7.2 in)
Compression Ratio
14.5:1
Aspiration
Air to Air Aftercooled
Governor Type
Adem™A4
Fuel System
Electronic unit injection
Fuel System
Electronic unit injection

Generator Set Specifications

Minimum Rating
500 ekW
Maximum Rating
600 ekW
Voltage
220 to 380 Volts
Frequency
60 Hz
Speed
1800 RPM

Generator Set Configurations

Emissions/Fuel Strategy
Low Fuel Consumption
  • Air Inlet
    • Air Cleaner
  • Cooling
    • Package mounted radiator
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Primary fuel filter with integral water separator
    • Secondary fuel filter
    • Fuel priming pump
  • Generator
    • Matched to the performance and output characteristics of Cat engines
    • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
    • IP23 Protection
  • Power Termination
    • Bus Bar
  • Control Panel
    • EMCP 4.2
  • Mounting
    • Rubber vibration isolators
  • Starting/Charging
    • 24 volt starting motor
    • Batteries
  • General
    • Paint - Caterpillar Yellow except rails and radiators gloss black
  • Exhaust
    • Industrial, Residential, Critical Mufflers
  • Generator
    • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
    • Anti-condensation heater
    • Oversize and premium generators
  • Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
  • Control Panels
    • EMCP 4.4
    • Local & remote annunciator modules
    • Load share module
    • Digital I/O module
    • Remote monitoring software
  • Starting/Charging
    • Battery chargers
    • Oversize batteries
    • Jacket water heater
    • Heavy-duty starting system
    • Charging alternator
  • General
    • The following options are based on regional and product configuration:
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    • UL 2200 package
    • EU Certificate of Conformance (CE)
    • CSA Certification
    • EEC Declaration of Conformity
    • Narrow, Wide or Skid Base
    • Sound attenuated, weather protective or high ambient weather protective enclosure
    • Enclosures: sound attenuated, weather protective
    • Single or dual wall integral fuel tanks
    • Single or dual wall sub-base fuel tanks
    • Integral & sub-base UL listed dual wall fuel tanks
    • Automatic transfer switches (ATS)