Chat with us, powered by LiveChat

Starting Small... Building Big! With Alban CAT Construction Equipment...

Learn More
C32 Generator Set with Upgradeable Packaging Specifications
Minimum Rating 910 kVA
Maximum Rating 1500 kVA
Voltage 220 to 4160
Frequency 50 Hz

Generator Set Specifications

Minimum Rating
910 kVA
Maximum Rating
1500 kVA
Voltage
220 to 4160
Frequency
50 Hz
Speed
1500 RPM
Height - Maximum
85.6 in
Length - Maximum
2179.2 in
Width - Maximum
87.8 in

Generator Set Configurations

Emissions/Fuel Strategy
Low Fuel Consumption, Low Emissions

Engine Specifications

Engine Model
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
145 mm (5.71 in)
Displacement
32.1 L (1958.86 in3)
Stroke
162 mm (6.38 in)
Compression Ratio
15.0:1
Aspiration
TA
Aspiration
TA
Governor Type
Adem™A4
Fuel System
MEUI
Fuel System
MEUI
Exhaust Flange Size - Internal Diameter
203.2 mm (8.0 in)
Air Inlet
Single element canister style with service indicator
Air Inlet
Single element canister style with service indicator
  • Air Inlet System
    • Single element canister type with service indicator
  • Control Panel
    • Control Features
    • EMCP 4.2
    • Communications
    • Programmable Protective Relaying Functions
    • Digital Indicators
    • Warning Shutdowns
  • Cooling System
    • Coolant drain line with valve
    • Caterpillar Extended Life Coolant
    • Low coolant level sensor
    • Radiator fan and fan drive
    • Fan and belt guards
    • ATAAC
  • Exhaust System
    • 203 mm (8 in) ID round flanged outlet
    • Exhaust manifold - Dry
  • Fuel System
    • Fuel priming pump
    • Fuel cooler
    • Secondary fuel filters
    • Primary fuel filter with water separator
  • General
    • Caterpillar Yellow with high gloss black rails & radiator
    • RH Service
    • SAE Standard Rotation
    • Flywheel and flywheel housing-SAE
  • Generators and Attachments
    • 3 Phase brushless
    • Reactive droop
    • Busbar connections, top center mounted, top cable entry
    • Internal excitation
    • Permanent magnet
    • Integrated voltage regulator (IVR)
    • Class H temperature rise at 40C ambient
    • Salient pole
    • Winding temperature detectors
    • 6 Lead
    • NEMA Class H insulation
    • IEC standard hole pattern
  • Governing System
    • ADEM(tm) A4
  • Lube System
    • Fumes disposal
    • Oil drain lines and valve
    • Lubricating oil
    • Gear type lube oil pump
    • Integral lube oil cooler
    • Oil filter, filler and dipstick
  • Mounting System
    • Rubber anti-vibration mounts
    • Rails - engine/generator/radiator mounting
  • Power Termination
    • Busbar
  • Starting / Charging System
    • 45 amp charging alternator
    • Battery, rack and cables
    • Battery disconnect switch
    • 24-volt electric starting motor
  • Control System
    • Expansion I/O module
    • EMCP 4.3, EMCP 4.4
    • Remote monitoring software
    • Local annunciator module
    • Remote annunciator module
  • Engine System
    • Heavy duty electric starting motors
    • Muffler (industrial grade)
    • Jacket water heater
    • Dual element air cleaners
    • Rubber anti-vibration mounts (90% efficient)
    • Battery charger (10 amps)
    • Heavy duty batteries
    • Exhaust guards / shields
    • Heavy duty air cleaners
    • Spring type anti-vibration mounts (95% efficient)
    • Radiator duct flange
  • Extended Service Contract
    • 2 Year Extended Service Contract (ESC)
    • 3 Year Extended Service Contract (ESC)
    • 5 Year Extended Service Contract (ESC)
  • Generators
    • Generator stator and bearing temperature monitoring & protection
    • Anti-condensation heaters
    • Temperature Rise over 40°C ambient: [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
    • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
    • Winding: [ ] Random [ ] Random with coastal insulation [ ] Form
  • Power Termination
    • Circuit breaker, 100% Rated, UL Listed (fully rated)
    • Bus bars
    • Circuit breaker, IEC listed (fully rated)