Cat XLM Switchgear Specifications
Configuration Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Configuration Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Modes of Operation Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Modes of Operation Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power

Technical Summary

Configuration
Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Configuration
Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application
LV and MV ( 208V - 38 kV
Application
LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications
IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure
NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature
0 degrees to 50 degrees C
Operating Temperature
0 degrees to 50 degrees C
Storage Temperature
-20 degrees C to +60 degrees C
Storage Temperature
-20 degrees C to +60 degrees C
Low Voltage Standards
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
  • Generator Demand Priority Control
    • Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.
  • Data Table Interface
    • Accommodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
  • Supplemental Hardware Synchronization check relay (ANSI 25 Device)
    • Provides additional discrete synchronization protection
  • Remote Power Monitoring System
    • To monitor breaker status, alarms, metering and other operating parameters