XQ2000 Specifications
Standby Rating 2000 ekW (2500 kVA)
Rating (1) 1400 ekW (1750 kVA) Continuous
Rating (2) 1600 ekW (2000 kVA) Prime
Prime Rating 1825 ekW (2281 kVA)

Generator

Standby Rating
2000 ekW (2500 kVA)
Rating (1)
1400 ekW (1750 kVA) Continuous
Rating (2)
1600 ekW (2000 kVA) Prime
Prime Rating
1825 ekW (2281 kVA)
Frequency
50 Hz
Voltage
240 - 480 V
Prime Run Time (Full Load)
9.8 Hrs

Engine

Engine
3516 Tier II ATAAC
Fuel
Diesel
Emissions
Non-Certified
Fuel System
EUI
Governor Type
Cat ADEM A4 Control System

Dimensions

Width
96.0 in
Height
114.0 in
Length
480.0 in
Weight
73000.0 lb
Height - With Chassis
168 in
Height - Without Chassis
114 in
Length - Without Chassis / With Chassis
480 in
Weight - With Chassis, Lube Oil and Coolant
74000 lb
Weight - Without Chassis, With Lube Oil and Coolant
64000 lb
Width - Without Chassis / With Chassis
97.5 in
  • Engine
    • Cat 3516B heavy duty flex fuel engine
    • Heavy duty, single element canister type air cleaner with service indicator
    • Fuel filters – primary and duplex secondary with integral water separator and change-over valve
    • Spin on, full flow oil filters with water cooled oil cooler. Requires API CF-4 lube oil
    • Stainless Steel Aftercooler core
    • Jacket water heater, 9kW, 400V, 50 Hz, 3-phase w/isolation valves
    • Fuel cooler and priming pump
    • Electronic ADEM A4 controls
    • Integrated Sensor Module (ISM) for combustion sensing and exhaust gas sensing
    • Dual 24V electric starting motors
  • Generator
    • Double bearing SR-4B brushless, form wound, permanent magnet excited, three-phase with Cat digital voltage regulator (Cat DVR), space heater, 6-lead design, Class H insulation operating at Class F temperature for extended life, winding temperature detectors and anti-condensation space heaters (120/240V 1.2 kW).
    • Generator equipped with System 4 insulation protection.
  • Containerized Module
    • 40' ISO high cube container, 9-High stack CSC certified
    • Four (4) sound attenuated air intake louvers and 3 lockable personnel doors with panic release
    • Interior walls and ceilings insulated with 100 mm of acoustic paneling
    • Floor of container insulated with acoustic glass and covered with galvanized steel
    • Side bus bar access door, external access load connection bus bars
    • Shore power connection via distribution block connections for jacket water heater, battery charger, space heaters, and generator condensate heaters
    • Six (6) DC lights
    • 1,250 gal fuel tank, UL listed, double wall, >13 hr runtime @ Continuous rating
    • Solenoid diesel fuel fill control valve
    • Lube oil level regulator with makeup tank
    • Sound attenuated 75 dB(A) @ 15 m (50 ft)
    • Four (4) oversized maintenance-free batteries, battery rack and 20-Amp battery charger
    • Critical grade exhaust silencer with dual 2 m (6.5 ft.) exhaust stacks for increased site power density
    • Vibration isolators, stainless steel fastening hardware and hinges
    • External drain access to standard fluids
    • One 4.5 kg (10lb) carbon dioxide fire extinguisher
    • Standard Cat rental decals and painted standard Cat power module white
    • 110% spill containment system for on-board engine fluids
    • Methane Leak Detection
  • Gaseous Fuel System
    • Low pressure regulator
    • Electronically actuated fuel control valve
    • Gaseous fuel heater
    • Electronically controlled gas shut-off valve
    • Gas induction nozzles
    • 1 micron gas fuel filter with dP sensors and isolation ball valve with 1” BSP drain plug for fluid build-up
    • CSA certified gas electronic components
  • Cooling
    • Standard cooling provides 43C (110F) ambient capability at 100% Prime
    • Horizontally mounted radiator with vertical air discharge
    • Variable frequency fan drive (VFD) for optimal partial load fuel consumption
  • Generator Controls and Protection
    • Controls provide auto paralleling AGC-4 controller, voltage and frequency adjust, base load / PF / load sharing / synchronizer, auto start / stop control & generator CB control, SCADA Interface (Ethernet), fuel level indications & alarms, fuel tank fuel transfer control
    • EMCP 4.3 genset mounted controller
    • Automatic start/stop with cool down timer
    • Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
    • Reverse compatibility for interface to legacy power modules
    • 3000A UL rated generator circuit breaker with LSIG trip unit w/ammeter
    • Multi-mode operation (island, multi-island and utility parallel), load sharing (multi-unit only)
    • Manual and automatic paralleling capability
    • Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchroscope
  • Quality
    • Factory testing of standard generator set and complete power module
    • UL, NEMA, ISO and IEEE standards
    • O&M manuals
  • EMCP 4.3 Local Control Panel
    • Generator mounted EMCP 4.3 provides power metering, protective relaying and engine and generator control and monitoring.
    • Convenient service access for Cat service tools (not included).
    • Integration with the Cat DVR provides enhanced system monitoring.
    • Ability to view and reset diagnostics of all controls networked on J1939 datalink eliminates need for separate service tools for troubleshooting.
    • Real-time clock allows for date and time-stamping of diagnostics and events.
    • Customer communication through Modbus TCP
    • True RMS AC metering, 3 phase: L-L volts, L-N volts, Phase, Amps, Hz, ekW, kVA, kVAR, kWHr, % kW, PF
  • EMCP 4.3 Engine Operator Interface
    • Graphical display with positive image, transflective LCD, adjustable white backlight/contrast.
    • Digital indication for
      • RPM
      • DC Volts
      • Operating hours
      • Oil pressure
      • Coolant Temperature
      • Oil Temperature
      • Gas Pressure
      • Gas Substitution %
      • Gas Shutoff Valve status
      • DGB Activation
    • Two LED status indicators (1 red, 1 amber)
    • Engine cool-down timer
    • Engine cycle crank
    • Three engine control keys and status indicators (Run/Auto/Stop).
    • Lamp test and Alarm acknowledgement keys
    • Warnings/shutdowns with indicating text for:
      • Low oil pressure
      • Overspeed
      • High Oil Temperature
      • Overcrank
      • Emergency stop
      • AGC-4
    • Emergency stop pushbutton
    • Display navigation keys including two shortcut keys for Engine Parameters or Generator Parameters
  • Container
    • 40' ISO high cube container, CSC 9-High Stack Certified
    • Painted standard Cat Power Module White per Caterpillar Specifications
    • Standard air intake louvers
    • Three (3) lockable personnel doors with panic release
    • Fire extinguisher
    • 110% spill containment system for on-board engine fluids
  • AGC-4/EMCP 4.3 Protective Relaying
    • Generator protective features
      • 25 sync-check ( AGC-4)
      • 32 rev. power (EMCP 4.3 and AGC-4)
      • 40 loss of excitation (Cat DVR and AGC-4 impedance based)
      • 50/51 Inst. and time overcurrent (GCB trip unit and AGC-4)
      • 47 Negative Voltage Sequence (AGC-4)
      • 46 Negative Sequence Current (AGC-4)
      • 27/59 phase under/over voltage (EMCP 4.3 and AGC-4)
      • 81O/U under/over frequency (EMCP 4.3 and AGC-4)
    • Package mounted AGC-4 controls provides auto paralleling, CAN-bus, Ethernet communications, PWM and Analog outputs, and legacy analog load sharing (real and reactive)
    • AGC-4 main display/ AOP secondary display
  • Voltage Regulation and Power Factor Control Circuitry
    • Generator mounted automatic voltage regulator, microprocessor based.
    • Manual raise/lower voltage adjust capability and VAR/power factor control circuitry, all via AGC- 4, for maintaining constant generator power factor while paralleled with utility
    • Includes RFI suppression, exciter limiter and exciter diode monitoring.
  • Current Transformers
    • CT's rated 3000:5 with secondaries wired to shorting terminal strips.
  • Circuit Breaker
    • 3000A fixed type, 3 poles, genset mounted, electrically operated, insulated UL489 CB.
    • Solid state trip unit for overload (time overcurrent) and fault (instantaneous) overcurrent protection. LSIG is standard.
    • Includes DC shunt trip coil activated on any monitored engine or electrical fault, 100 KAinterrupting capacity at 480 VAC.
    • Undervoltage Release 24vdc
    • Optional External Ground fault sensing/trip (requires additional ground CT)
  • Internal Lighting
    • Six (6) internal 24VDC LED lights with timers located at the control area personnel door
    • One (1) duplex service receptacle
  • Battery Charger and Batteries
    • 24 VDC/20A battery charger with float/equalize modes and charging ammeter
    • Four oversized maintenance free batteries
  • Emergency Stop Pushbutton
    • Single emergency stop pushbuttons (ESP) located on rear face of generator set controls area
    • Emergency Stop pushbutton located on the container exterior at each personnel door(3)
  • Exhaust Silencer
    • Critical grade, internally mounted, dual cylindrical exhaust silencers
    • 2 m high vertical discharging exhaust stack located in radiator discharge area
  • Fuel Tank
    • UL Listed 1250 gallon double walled tank
    • Fuel solenoid valve system
    • Triple fuel/water separators
  • Modes of Operation
    • Provides for single unit stand-alone operation, island mode paralleling and load sharing with other power modules, and single unit-to-utility mode paralleling for base load control (with open transition between paralleling modes)*
    • Island mode paralleling features:
      • AGC-4 control allows single unit to connect to a dead bus
      • Auto synchronization (voltage & phase matching)
      • Load sharing (kW) analog signal (like units & legacy compatible)
      • Load sharing (kVAR) analog signal (like units only)
    • Utility mode paralleling features:
      • Auto synchronization (voltage & phase matching)
      • Base-load control (selectable: programmable set-point or potentiometer adjust)
      • Soft load/unload (programmable, shared setpoint)
      • Power Factor control (programmable setpoint)
  • Bus Bars
    • Three phase, plus full rated neutral, bus bars are tin-plated copper with NEMA standard hole pattern for connection of customer load cables and generator cables.
    • Bus bars are sized for full load capacity of the generator set at 0.8 power factor.
    • Includes ground bus, tin-plated copper, for connection to the generator frame ground and field ground cable.
  • AC Distribution
    • 3 phase, 400VAC, 50 Hz, 50 amp input which can be derived from either the Power Module main output bus (Internal) or customer supplied shore power (External) via selector switch.
    • Onboard 50 Hz Transformer for the Power Module AC auxiliaries provides 240/120 VAC for all module accessories except Jacket water heater (400V). Includes controls to de-energize jacket water heaters and generator space heater when the engine is running
  • Lube Oil Make-Up System
    • Includes oil pan-mounted oil level regulator and 114 L (30 gal) oil tank for maintaining oil pan levels in extended run applications. Oil tank can be remotely filled without shutting down the engine.
  • Trailer
    • Three axle with Anti-lock brake system
    • Goodyear G314 295/75R225 Load Range G